ZW7B-40.5 Outdoor Vacuum Circuit Breaker

ZW7B-30kV(40.5kV) Outdoor Vacuum Circuit Breaker

This series of outdoor high-voltage vacuum circuit breakers adopts a uniquely designed split pole and a highly reliable spring operating mechanism or permanent magnet operating mechanism. This device is mainly used in medium voltage overhead lines The power grid is used to divide and combine load current, overload current and short-circuit current. It can also be used in the circuit of high-voltage SVG energy storage power station as the main incoming line switch.

Feature
1

This outdoor high-voltage vacuum circuit breaker is mainly composed of integrated poles, current transformers, operating mechanisms, mechanisms and boxes.

2

This model of circuit breaker is miniaturized in design and its casing is made of high-quality steel box. Current transformers can be selected according to user needs.

3

The circuit breaker can be combined with matching intelligent control. The switch opening and closing operation can be realized locally or remotely controlled through the communication interface.

4

Other information of the circuit breaker can also be transmitted to the control center, and the communication channel can choose cable, optical fiber, GPRS/CDMA, GSM, etc.

Parameter

Project

Unit

Data

Rated voltage

kV

40.5

Rated current

A

630/1250/1600

Rated frequency

Hz

50/60

Power frequency withstand voltage for 1 minute (wet) (dry) phase to phase, ground/fracture

kV

80 95 / 95

Lightning impulse withstand current (peak) phase to phase, ground/fracture

kA

185

Rated short circuit opening current

kA

25/31.5

Rated short circuit making current (peak value)

kA

63/80

4S short-term withstand current

kA

25/31.5

Rated operating cycle

Divide - 0.1s - Divide together - 3s - Divide together - 6s Divide together - 60s recovery

Rated short circuit current breaking times

Second-rate

30

Mechanical life

Second-rate

10000

Mechanism control voltage

V

AC/DC220

Secondary circuit 1min power frequency withstand voltage

kV

2

Contact spacing

mm

18±1

Contact overtravel

mm

4±0.5

Opening speed

m/s

1.4-1.8

Closing speed

m/s

0.4-0.8

Contact closing bounce time

ms

≤5

distance between centers

mm

710±2

Different phases of three-phase opening and closing

ms

≤2

Conductive loop resistance of each phase

μΩ

<80

Closing time

ms

≤100

Opening time

ms

≤50

Weight

KG

800



Install