Home - Products Center - Vacuum Circuit Breaker - Outdoor Vacuum Circuit Breaker - ZW7-30kv(40.5kv) Outdoor High Voltage Vacuum Circuit Breaker
Back
ZW7-40.5 Outdoor High Voltage Vacuum Circuit Breaker
ZW7-40.5 Outdoor High Voltage Vacuum Circuit Breaker

ZW7-30kv(40.5kv) Outdoor High Voltage Vacuum Circuit Breaker

This product is suitable for a 30KV(40.5KV), 50HZ three-phase distribution system and can effectively handle load switching currents, overload currents, and short-circuit currents. Additionally, it can serve as the main incoming switch for medium-voltage SVG-enabled power stations, suitable for locations below 2000 meters in altitude, with a spacing of 710mm, and supports custom dimensions to meet installation requirements above 4500 meters.

Feature
1

Product Mainly composed of an integrated pole, current transformer, operating mechanism, and enclosure.

2

Product uses vacuum as both the insulating medium and arc-extinguishing medium, making it an ideal product to replace DW oil circuit breakers.

3

The dimensions are reduced by 260mm compared, making it suitable for installation in spaces with limited positions.

Parameter

Tech. parameters unit data
Rated voltage KV 40.5
Rated insulation level
1min power frequency withstand voltage Dry test KV 95
(Effective values) Wet test KV 80
Lightning impulse withstand voltage (peak) KV 185
Rated current A 1250/1600/2000
Rated short-circuit breaking current KA 20/25/31.5/40
Rated sequence of operations min-0.3s-combine-180s-combine
Rated capacitor bank breaking current A 400
Rated breaking times of short-circuit breaking current Times 30
Rated short-circuit closing current (peak) KA 50/63/80/100
Rated peak withstand current KA 50/63/80
Rated short-time withstand current KA 20/25/31.5/40
Rated short-circuit duration S 4
Total breaking time S ≤0.08
Mechanical life times 20000
Rated operating voltage and rated voltage of auxiliary circuit V AC, DC 220, 110
Clearance between open contacts mm 22±2
Contact contact stroke mm 4±1
Average breaking speed m/s 1.7±0.2
Average making speed m/s 0.7±0.2
Contact closing bounce time ms ≤3
The three phases non-synchronism ms ≤2
Closing time ms ≤150
Opening time ms ≤60
The DC resistance of each phase circuit (mΩ) ≤100

Environmental conditions:
1.Ambient air temperature: +60℃ to -30℃
2.Altitude not exceeding 2000m
3.Wind pressure not exceeding 700Pa (equivalent to wind speed of 34m/s)
4.No frequent severe movements
5.Air pollution level: Grade III