XGW-12KV environmental protection gas insulated ring main unit / primary and secondary fusion complete sets of ring main unit
XGW-12KV environmental protection gas insulated ring main unit / primary and secondary fusion complete sets of ring main unit

Gas insulated switchgear (Switchgear)

XGW-12 environmental protection gas insulated ring main box, is the pure air / nitrogen (environmental protection gas) ring main unit, current transformer, voltage transformer, automation station terminal (DTU) and indicating instruments installed and debugged into a movable, sealed, moisture-proof and condensation-proof box, so as to realize the integration of the primary and secondary systems in the urban distribution network, shorten the construction period, and greatly improve the reliability of the operation of the urban power grid.

Feature
1

The environmental protection gas insulated ring main unit can be used unit cabinet or common box scheme pure air/nitrogen (environmental protection gas) ring main unit, the typical scheme has two in and two out, two in and four out of the cabinet combination, can also be designed and produced according to user requirements of more unit combination of customized ring main unit.

2

The outer box is made of stainless steel, sprayed cold-rolled plate and GRC, and the outer box of landscape or spray painting can also be produced according to the needs to better integrate with the surrounding environment.

3

The dimensions and performance indicators of the outdoor environmental protection gas insulated ring main unit meet the requirements of "12,000 volt ring main unit (box) standardized design customized scheme (2019 edition)", GB/T17467 "high voltage/low prefabricated substation" and IEC466: "AC insulated enclosed switchgear and control equipment with rated voltage above 1KV and below 38KV".

4

The product has the characteristics of low carbon, environmental protection, reliability, safety and compactness.

Parameter

Electricity  Circuit breaker cabinet Load switchgear
Projects unit numeric value
Rated voltage  kV 12
Rated frequency  Hz 50   60
Current rating  A 630     1250
Arc extinguishing method / vacuum
Insulation method  / Pure air/pure nitrogen (Note: Pure air/pure nitrogen refers to the preparation of synthetic high-purity air or nitrogen with a moisture content of less than 15ppm)
Rated power frequency To the ground, interphased kV 42
Withstand voltage Between the fractures kV 48
Rated for lightning To the ground, interphased kV 75
Impulse voltage Between the fractures kV 85
Short-term tolerance Main circuit kA/s 20/4  25/4
Ground loop kA/s 17.4/2
Peak rating Main circuit kA 50    63
Withstands currents Ground loop kA 43.5
Rated short-circuit closing current (peak)  kA 50    63
Rated short-circuit interrupting current  kA 20   25 /
Rated short-circuit breaking current, breaking times, E2 level  Times 30 /
Circuit breaker unit rated operating sequence  / 0-0.3s-C0-180s-C0 /
Rated cable/line charging breaking tes / C2级 /
Out-of-phase ground fault interrupting current kA 17.4 /
Rated active load breaking current A / 630
Rated closed-loop interrupting current  A / 630
Rated cable charging breaking test A / 10
5% rated active load switch breaking current A / 31.5
The number of times the ground switch is closed  Times 5 (Note: XGN118C-12, XGN118D-12 series of lower separation height grounding scheme is 2 times)
Loop resistance μΩ ≤140
Rated gas pressure (20°C gauge) Mpa 0.02
Minimum operating gas pressure
MPa 0
Mechanical life Circuit breakers/load switches Times 10000    30000
Disconnector Times 3000   6000
Grounding switch Times 3000   6000
Ingress protection Airbox / IP67
enclosure / IP4X
Rated annual air leakage rate  % 0.01
Resistant to internal arc faults  kA/s 20/0.5(20/1) 25/0.5(25/1)
The moisture content in the airbox ppm ≤150
Environmental conditions of use
  1. Ambient temperature: upper limit +55°C, lower limit -40°C.
  2. Altitude: no more than 3000m.
  3. Relative humidity: the daily average value < 95%, the monthly average value ≤ 90%.
  4. Water vapor pressure: daily average ≤ 22kPa; The monthly average ≤ 1.8kPa.
  5. Workplace: The surrounding air is not visibly polluted by dust, smoke, corrosive and/or combustible gas, steam or salt spray; There is no fire explosion, serious pollution, serious chemical corrosion and severe vibration.
  6. The amplitude of electromagnetic interference induced in the secondary system ≤ 1.6kV.
  7. Note: When the altitude is greater than 3000m or under special use conditions, customized product solutions are required.