XGW-12KV environmental protection gas insulated ring main unit / primary and secondary fusion complete sets of ring main unit
XGW-12KV environmental protection gas insulated ring main unit / primary and secondary fusion complete sets of ring main unit

Gas insulated switchgear (Switchgear)

The Gas insulated switchgear is an integrated power device specifically designed for urban distribution networks. It incorporates a clean air or nitrogen (eco-friendly gas) ring network cabinet, current transformers, voltage transformers, an automated station terminal (DTU), and indicating instruments into a mobile, sealed, moisture-proof, and condensation-proof enclosure. This design significantly shortens the construction period and enhances the operational reliability of urban power grids.

Feature
1

Modular Design: It can use unit cabinets or shared box schemes, supporting various combinations such as two in two out, two in four out, and can even customize more unit combinations based on user requirements.

2

Diverse Outer Box Materials: The outer box can be made from stainless steel, spray-painted cold-rolled steel, or GRC materials. It can also be customized to create landscape-style or printed-pattern outer boxes, facilitating integration with the surrounding environment.

3

Standardized Performance: The dimensions and performance indicators meet the requirements of IEC 466, which specifies the rated voltage of above 1KV and below 38KV for AC insulated enclosed switchgear and control equipment.

4

Eco-friendliness and Safety: The product features advantages such as low carbon emissions, eco-friendliness, reliability, safety, and compactness, meeting the needs of modern urban development.

Parameter

Switchgear model
Circuit breaker cabinet Load switchgear
Projects Unit Value
Rated voltage  kV 12
Rated frequency  Hz 50   60
Rated current A 630     1250
Arc extinguishing method / Vacuum
Insulation method  / Pure air/pure nitrogen (Note: Pure air/pure nitrogen refers to the preparation of synthetic high-purity air or nitrogen with a moisture content of less than 15ppm)
Rated power frequency To the ground, interphased kV 42
withstand voltage Between the fractures kV 48
Rated lightning impulse  To the ground, interphased kV 75
withstand voltage Between the fractures kV 85
Short-term  Main circuit kA/s 20/4  25/4
withstand current Ground loop kA/s 17.4/2
Rated peak
Main circuit kA 50    63
withstands current Ground loop kA 43.5
Rated short-circuit making current (peak)  kA 50    63
Rated short-circuit breaking current  kA 20   25 /
Rated breaking times of short-circuit breaking current, E2 level  Times 30 /
Circuit breaker unit rated operating sequence  / 0-0.3s-C0-180s-C0 /
Rated cable/line charging breaking test / C2 class /
Different phases earth fault breaking current kA 17.4 /
Rated active load breaking current A / 630
Rated closed-loop breaking current  A / 630
Rated cable charging breaking test A / 10
5% rated active load switch breaking current A / 31.5
The making and breaking times of the earthing switch Times 5 (Note: XGN118C-12, XGN118D-12 series of lower separation height grounding scheme is 2 times)
Loop resistance μΩ ≤140
Rated gas pressure (20°C gauge) Mpa 0.02
Minimum operating gas pressure
MPa 0
Mechanical life Circuit breakers/load switches Times 10000    30000
Disconnector Times 3000   6000
Grounding switch Times 3000   6000
Ingress protection Airbox / IP67
enclosure / IP4X
Rated annual air leakage rate  % 0.01
Resistant to internal arc faults  kA/s 20/0.5(20/1) 25/0.5(25/1)
The moisture content in the airbox ppm ≤150
Environmental conditions of use
  1. Ambient temperature: upper limit +55°C, lower limit -40°C.
  2. Altitude: no more than 3000m.
  3. Relative humidity: the daily average value < 95%, the monthly average value ≤ 90%.
  4. Water vapor pressure: daily average ≤ 22kPa; The monthly average ≤ 1.8kPa.
  5. Workplace: The surrounding air is not visibly polluted by dust, smoke, corrosive and/or combustible gas, steam or salt spray; There is no fire explosion, serious pollution, serious chemical corrosion and severe vibration.
  6. The amplitude of electromagnetic interference induced in the secondary system ≤ 1.6kV.
  7. Note: When the altitude is greater than 3000m or under special use conditions, customized product solutions are required.