KYN28A-12 Indoor Withdrawable Medium-Voltage Switchgear is a complete indoor distribution device for three-phase AC with a rated voltage of 3.6–12 kV and a frequency of 50 Hz. It is used for power delivery in power plants, electrical systems, and substations in industrial enterprises, as well as for frequently starting medium-voltage motors. This switchgear meets the requirements of standards IEC-298, and features five protective functions: preventing erroneous operation of the circuit breaker, preventing the trolley from being pushed or pulled under load, preventing the grounding switch from closing under load, preventing power delivery when the grounding switch is in the grounded position, and preventing accidental access to live compartments.

Feature
1

The switchgear consists of 2 parts: a fixed cabinet body and a withdrawable section (trolley).

2

The cabinet shell and partition plates of each functional unit are made from bolted aluminum-zinc coated steel plates.

3

The protection level of the switchgear's shell reaches IP4X, while the protection level of each compartment is IP2X when the door is open.

4

This switchgear can be equipped with VS1 (ZN63A) or other specified vacuum circuit breaker trolleys according to user requirements.

5

Since installation, commissioning, and maintenance can be performed from the front of the cabinet, it can be arranged back-to-back in a double configuration or mounted against a wall.

Parameter

Number  Tech. parameters
Unit Data
1 Rated voltage KV 3.6/7.2/12
2 Rated current A 630.1250,1600.2000.2500,3150.4000
3 Rated frequency Hz 50-60
4 Rated short-circuit breaking current KA 20,25,31.5,40,50
5 Rated dynamic stability current (peak) KA 50,63,80,100,125
6 Thermal Stability Current (4s) KA 20,25,31.5,40,50
7 Insulation level: power frequency/lightning impulse kv 42/75
8 Ingress protection IP4X
9 Configured circuit breaker ZN63A(VS1)、VD4、VEP、EV12etc
10 Operating mechanism Permanent magnet mechanism, spring mechanism
11 Operating voltage V DC:110,220;AC:110,220
12 Dimensions (WxDxH) mm 800(650,1000)×1500(1700)x2300
13 Weight Kg 800
Environmental Conditions for Use
1. Surrounding Air Temperature: +40°C to -10°C. The average temperature within 24 hours should be ≤ +35°C.
2. Relative Humidity: Daily average relative humidity ≤ 95%, monthly average relative humidity ≤ 90%. Daily average water vapor pressure ≤ 2.2 kPa, monthly average water vapor pressure ≤ 1.8 kPa.
3. Altitude: The elevation of the installation site should be ≤ 2000 m.
4. Seismic Intensity:  The maximum seismic intensity should not exceed 8 degrees.
5. Installation Conditions:  The switchgear should be installed in indoor locations free from fire hazards, explosion risks, severe dirt, corrosive gases, and significant vibrations. The design should meet rigorous standards under harsh conditions.
6. Condensation Control:  In humid and temperature-variable regions, condensation may occur inside the switchgear. A dehumidification controller and heater can be configured as needed to maintain an automatically controlled environment, preventing equipment from becoming damp and avoiding condensation.
7. Special Requirements:  If users have specific requirements, please consult with us.


Main Features
1. The cabinet structure is made from aluminum-zinc coated steel plates assembled through multiple bends.
2. All operations are conducted with the cabinet doors closed.
3. High protection level prevents the intrusion of debris and pests.
4. A simple and effective "Five prevention" locking mechanism to prevent erroneous operations.
5. Compatible with VS1 (ZN63A) or other specified vacuum circuit breakers as per user requirements.
6. Circuit breaker replacement is simple, with good interchangeability of trolleys.
7. The cabinet can be reliably installed against a wall, allowing for front maintenance and reducing the footprint.
8. The cable room has ample space for connecting multiple cables.
9. A quick grounding switch is provided for grounding and short-circuiting.
10. The circuit breaker room, relay room, and cable room can be equipped with heaters upon user request to prevent condensation and corrosion.
11. The circuit breaker room and cable room can be equipped with lighting devices upon user request to facilitate maintenance and repairs.

Related Products