Bypass Switch (High Performance Switch)
The CNF series vacuum switch is used for bypass protection of power electronic semiconductor devices. The main contact of the bypass switch is connected in parallel with the power electronic semiconductor device. During normal operation, the main contact of the bypass switch is open. When the power electronic semiconductor device fails, power is supplied to the coil, quickly closing the main contact of the bypass switch, thereby bypassing the power electronic semiconductor device and allowing the system to continue operating. It is commonly used in flexible DC transmission and transformation equipment as a bypass switch.
The main contact of the bypass switch is connected in parallel with the power electronic semiconductor device.
During normal operation, the main contact of the bypass switch is open. When the power electronic semiconductor device fails, power is supplied to the coil, quickly closing the main contact of the bypass switch, thereby bypassing the power electronic semiconductor device and allowing the system to continue operating.
1. Closing speed ≤ 3.5 ms, with no bounce.
2. Main circuit current: 400A~2500A; wide voltage range: 1.14KV~3.6KV.
3. Mechanical holding function after actuation and manual reset function.
4. Features an easy-to-operate mechanical unlocking structure (from closed to open).
5. The shell and leads use environmentally friendly, flame-retardant materials (UL94-VO).
6. Adopts a fully enclosed structure with good insulation performance, compact size, and suitable for various installation scenarios
Tech. parameters | Model | 400 | 630、800 | 1250 | 1600 | 2000/2500 |
Rated voltage of the main circuit | (V) | 1140 | 3600 | 3600 | 3600 | 3600 |
Rated current of the main circuit | (A) | 400 | 630、800 | 1250 | 600 | 2000/2500 |
Short duration power frequency withstand voltage | (KA) | 4 | 6.3、8 | 12.5 | 16 | 25 |
Ultimate breaking capacity | (A/3times) | 4000 | 6000 | 10000 | 0 | 10000 |
Electrical life | (10,000times) | 1 | 1 | 1 | 1 | 1 |
Mechanical life | (10,000times) | 10 | 10 | 10 | 10 | 10 |
Clearance between open contacts | (mm) | 1.5±0.5 | 3±0.5 | 3±0.5 | 3±0.5 | 3±0.5 |
Overtravel | (mm) | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 |
Closing time | (ms) | ≤3 | ≤3 | ≤3 | ≤3.5 | ≤3.5 |
Bounce time | (ms) | ≤1 | ≤1 | ≤1 | ≤2 | ≤2 |
Secondary control voltage | (V) | AC or DC:36/110/127/220/380or customized |
VCN3-10kV(12kV) Series Handcart Vacuum Contactor
VCN3-10kV(12kV) Series Handcart Vacuum Contactor is a new ...
See MoreVCNR-10kV(12kV) Handcart Vacuum Contactor with Fuse
This series of products is suitable for three-phase indoor ...
See MoreHorizontal High Voltage Vacuum Contactor
The VCH series horizontal high-voltage vacuum contactor is ...
See MoreProduct Search
Here you can choose products online and find the products you want more quickly and accurately.
Customized Consultation
If you want to customize a product, please contact us, and our team is more than happy to assist you.
Product Procurement
If you want to purchase a product, please contact us and we will provide you with product information and a quotation.
Tel:+86 15538537280
Email:lycnelectric@163.com
Add:No. 9 Duyu Street, Luolong District, Luoyang City, Henan Province